CA 42

Signal conditioners for transmitters

General

The CA-42 is an isolated signal conditioner that powers a two-wire transmitter through a 4 to 20 mA current loop. Through the same loop, the conditioner measures events from the transmitter. In addition, the CA-42 protects, filters, amplifies, isolates the signal and converts it to a level suitable for connection to a data acquisition system, Industrial PC, PLC, panel meter or other measuring system.

CA-42 family of isolated modules protect people and measuring equipment and electrically isolate it from excess events that may occur on the sensor side or elsewhere within the measurement environment. The module input is protected against overvoltage up to 250 Vrms.

The CA-42 conditioner family can be mixed with other isolatied signal conditioner families within the same application. They can be connected and disconnected without interrupting the power or stopping the system (hot swapable).

Prices and models of CA-42

Atributes

  • Sensor supply via 4 to 20 mA current loop
  • Exit exit loop isolated
  • Voltage Output: 0 ÷ 5V; 0 ÷ 10 V; ± 5 V; ± 10 V, or
  • Current output: 0 ÷ 20 mA; 4 ÷ 20 mA; ± 5 mA; ± 10 mA; ± 20 mA
  • Linearity ± 0.01%
  • Accuracy ± 0.03%
  • Input continuously protected up to 250 Vrms
  • Quadruple insulation: input-output-excitation-power
  • Isolation input to output min. 1500 Vrms (4000 V, 1 minute)
  • 105 dB CMR and 80 dB NMR for 50 Hz
  • 5th order Low Pass filter
  • Easy mounting on DIN rail
  • Power supply of conditioner from 19 V to 30 V (24 V nominal)
  • Transient protection by ANSI / IEEE C37.90.1-1989 specification
  • The warranty period is 7 years and the service period is 10 years
 

Simplified diagram of CA-42

Characterisation

The central component of the module is the signal isolation transformer. Like most transformers, this one has a primary and a secondary side. Using this terminology, the input side of the module is "primary side" and the output side of the module is called "secondary side". A sensor is connected to the primary side of the module and the secondary side of the module is connected to a data acquisition and measurement system, an analog input module of an Industrial PC or PLC, to a panel meter or other measuring system.

Transformer signal isolation uses an amplitude modulation method to obtain linear, stable and reliable characteristics. This technique produces better results than digital or linear optocouplers or capacitor isolation techniques. The primary side of the module is galvanically isolated or "floating" relative to the secondary side of the module and relative to the power supply. The signal demodulator on the secondary side of the module restores the original signal, which is then filtered and buffered to achieve low noise and low output impedance.

CA-42 series isolated modules have a fifth-order filter built in. The first anti-aliasing filter being located in the primary circuit of the module while a fourth-order filter is located on the secondary side of the isolation barrier. After anti-aliasing filtering, the signal is brought to the chopper stage behind which is a specially designed micro transformer. On the secondary side, behind the isolation barrier, the signal is demodulated and re-filtered from transmission spikes and interference. The output of the module can be a voltage or current signal as needed.

Voltage excitation ensures accuracy within 1%. The voltage regulation circuit is galvanically isolated from the output and power supply and is protected from external voltages up to 250Vrms. For higher voltages, protection is applied which shorts the output terminals without harming the excitation circuit.

The warranty period is 7 years and the service period is 10 years. It comes with a user guide in English and a calibration list.

CA-42 with 110/220V AC power supply (option)

The basic version of the CA-42 works with a standard DC power supply of 19 to 30V DC (24V DC nominal). However, if the application requires power from 110V or 220V AC mains, which is not a rare case, then the user can order the conditioner with suffix A.

This type of signal conditioner works with an AC voltage of 85 to 265V or a DC voltage of 100 to 400V. These two power ranges make the CA-42 applicable in many situations. Some users use these conditioners in an environment powered by a 110V battery, or under conditions of elevated AC voltage in the substations.

There are three power connectors on this conditioner model: L, N and GND (Left picture). Phase must be connected to L, N to zero, and GND to ground. In addition to the safety function, grounding has the function of reducing the oscillations of the internal voltage unit, so it should be connected in any case. If DC power is used, it must be connected to the L and N terminals (order does not matter).

Relay (option)

The CA-42 R-type isolated family of conditioners has a built-in relay with normaly open and normaly closed contact on the external connections. The relay can turn on or off up to 240V, 6A, and can be set to activate when the input signal is larger than the set value or when it is less than the set value.  A hysteresis control is installed for the relay. Activation can be fine-tuned with a precision multi-turn trimmer potentiometer. The only limitation with this version is that if it is used with 220V power supply (version with suffix A), the relay only has a normaly open contact.

The activation level of the relay is adjusted by a potentiometer on the front of the conditioner. To avoid oscillating the relay when the input is equal to the setpoint, there is a hysteresis in the circuit. Hysteresis in the first case, when the relay is activated and when the input is greater than the set value, indicates the level by which the input signal should be smaller than the set size to activate the relay to switch it off, In the second case, indicates how much the input signal should be higher than the set point to turn the relay off. The hysteresis can be adjusted to 1% or 5% of the span by an internal jumper.

If the load that is connected to the relay is inductive, then a "snubber" must be added externally parallel to the relay contacts. The values ​​of the snubber components are calculated, but can also be determined empirically for a given application. Generally, even if the load is connected to an inductive type relay, a 0.2 uF capacitor can be used with a 10 ohm resistor. For optimum performance, the snubber circuit should be calculated as it is the best way to optimally quench the spark on the relay.

Power supply and T-BUS connector

For the power supply of a smaller number of conditioners up to 20, a CS-24-48 that delivers 48W is recommended (picture on the left), and for greater number of conditioners a CS-24-90 of 90W should be used. Both models can, via the T-BUS connector be connected, directly, without wiring to power the conditioners on the same, or with the extension cable, on different DIN rails in a closed environment. This option raises reliability, greatly reduces the time of replacement of the conditioner and allows the conditioner to be connected or disconnected while the T-BUS is powered up.

Both power supplies work in a wide voltage range: CS-24-90 from 160V to 265V AC, while smaller, CS-24-48 can operate as much as 85V to 265V. If users do not want to use this type of power supply, they can also use other power supplies, but in this case, the power supply must be wired from one conditioner to the other by cables.

Picture on the left: Power supply CS-24-48 for conditioners with T-BUS connector

 

The printed circuit board of the conditioner on request can be protected with special lacquer which protects electronic components from moisture, corrosion and other types of contamination, which can significantly extend the life of this product and in terms of long-term measurement accuracy. When conditioner is prepared in this way it can be applied in many aggressive environments. For example: on ships or on the seashore, in conditions of aggressive vapors, and other places with high humidity, etc...

 

Specifications

Typical (25°C)

 

 Parameter 

CA-42

 Input
 Input range 4 to 20 mA, current loop
 Input protection 250 V rms max. except input shunt
 Input resistance <100 Oma
 Input resistance, unpowered <100 Oma
Transient protection ANSI/IEEE C37.90.1
 Output
 Maximum load 500 Ω
 Current limit (Iout) 5 mA (Vout), 30 mA (Iout)
 Short circuit protection Continuous
 Transients ANSI/IEEE C37.90.1- 1989
 CMV, In-Out, In-power Continuous 1500 V rms max. (4000 V 1 minute)
 CMV, Out-power 1000 V DC
 CMR 50Hz  110 dB
 Reverse polarity protection Continuous
 General
 Accuracy 25 °C (including repeatibility) ±0.03% of span
 Non-linearity ±0.01% of span
 Adjustabillity ±1.5% offset & ±2.5% gain - typical
 Offset stability ±5 ppm/°C (Vout), ±20 ppm/°C (Iout)
 Gain stability ±35 ppm/°C
 Output noise 100 KHz 400 µVrms (Vout) & 1 µArms (Iout)
 Frequency range (-3 dB)  100 Hz
 Response time, span 90%  5 ms
 NMR 100 dB
 Power supply  
 Voltage Od 19  V do 30 V jednosmerno
 Current consumption 60 mA (Vout) i  80 mA (Iout)
 Power supply sensitivity 0,0002%
 Transient protection ANSI/IEEE C37.90.1- 1989

 Environment

 Working temperature range -40 do +85 °C
 Storage temperature range -40 do +85 °C
 Humidity Non-condensing 0 do 90%
 Mounting rail DIN EN50022 mm  -35 x 7,5;  -35 x 15
 Dimensions mm 114.5 x 22.5 x 99

 